Supermarket & Retail Kitchens

PT-Type Condenser for Industrial Refrigeration Systems

  • Fresh
  • Durable
  • Customizable

The PT-Type Condenser is designed for refrigeration heat rejection and features a service-oriented construction intended to simplify tube-bundle inspection, cleaning and maintenance.

  • Listed heat rejection capacity 48–396 kW across the source-listed models
  • Airflow range 12,200–115,070 m³/h across the source-listed models
  • Removable Tube-Bundle Design
  • Maintenance-Oriented Construction
  • Multiple Capacity Configurations
  • Fan and Electrical Options
  • Flexible Installation
  • Chilled or Frozen Transport
  • Portable Design
  • Power Flexibility
PT-Type Condenser for Industrial Refrigeration Systems Get a Quote
Overview

A Service-Friendly Condenser for Refrigeration Applications

A condenser rejects heat from a refrigeration system as refrigerant releases energy and changes from vapour to liquid under the required operating conditions. The PT-type design described in the source material emphasizes a flange-connected tube-bundle assembly that can be withdrawn from the housing for inspection, cleaning or repair. This arrangement may be valuable in applications where fouling, planned maintenance and equipment uptime are important considerations.

View Specifications
Containerized cold room being crane-lifted onto a concrete base at a distribution site
  • Removable Tube-Bundle Access

    The source description states that the tube bundle can be removed from the housing through a special flange connection. This can make detailed inspection and cleaning easier, subject to the approved maintenance procedure and sufficient withdrawal clearance.

  • Heat-Rejection Performance

    The source table lists nominal capacity figures from 48 kW to 396 kW. These values are transcribed from the page and should be checked against the manufacturer’s rated conditions before being used for equipment sizing.

  • Fan-Driven Airflow

    The model table includes airflow and fan-speed values, indicating that fan performance is part of the published configuration. Confirm whether airflow is stated per fan or for the complete unit before comparing models.

  • Motor Wiring and Electrical Data

    The source lists delta and star (Y) wiring options and provides power and current values. The required wiring arrangement, voltage, frequency, protection and control method should be confirmed against the nameplate and wiring diagram.

  • Service Planning and Fouling Control

    Where deposits or contamination may affect heat transfer, routine inspection and cleaning can help maintain performance. Maintenance intervals should be determined from operating conditions, water or refrigerant quality, and the manufacturer’s instructions.

  • Industrial System Integration

    The product may be evaluated for compatible industrial refrigeration, process cooling or central cooling applications. Confirm the actual heat-transfer medium, refrigerant compatibility, pressure rating and installation requirements before specifying the equipment.

Specifications

Technical Specifications

Reference configuration for the two standard sizes. Dimensions, refrigeration capacity and electrical supply are confirmed for each project in the quotation drawing.

Model

Motor Wiring

Heat Rejection at Δt = 15 K (kW)

Airflow (m³/h)

Fan Speed (r/min)

Total Power (W)

Current (A, Source Label Interpretation)

Noise at 10 m (dB(A))

Inlet / Outlet Connection (mm)

LPT66-801

Delta

66

18,660

890

1,800

3.8

52

42/35

LPT60-801

Y

60

14,140

660

1,150

2.2

46

Not listed

LPT58-801

Delta

58

14,770

670

800

1.95

45

42/35

LPT48-801

Y

48

12,200

670

490

1.0

41

Not listed

LPT109-802

Delta

109

39,000

890

3,600

7.6

54

42/35

LPT99-802

Y

99

29,680

660

3,600

2.2

48

Not listed

LPT96-802

Delta

96

30,120

670

1,600

3.9

47

42/35

LPT79-802

Y

79

24,920

670

1,600

3.9

43

Not listed

LPT132-802

Delta

132

37,320

890

2,300

4.4

54

54/42

LPT120-802

Y

120

28,280

660

2,300

4.4

48

Not listed

LPT116-802

Delta

116

24,400

670

980

2.0

47

54/42

LPT96-802

Y

96

45,180

670

980

2.0

43

Not listed

LPT165-803

Delta

165

58,500

890

5,400

11.4

56

54/42

LPT150-803

Y

150

44,520

660

5,400

11.4

50

Not listed

LPT145-803

Delta

145

37,380

670

2,400

5.85

49

54/42

LPT120-803

Y

120

44,310

670

2,400

5.85

45

Not listed

LPT198-803

Delta

198

55,980

890

3,450

6.5

56

54/42

LPT180-803

Y

180

42,420

660

3,450

6.6

50

Not listed

LPT174-803

Delta

174

36,600

510

2,400

3.0

49

54/42

LPT144-803

Y

144

56,080

510

1,470

3.0

45

Not listed

LPT144-804

Delta

264

74,640

890

7,200

15.2

57

67/54

LPT240-803

Y

240

56,560

660

4,600

8.8

51

Not listed

LPT232-804

Delta

232

48,800

510

1,470

7.8

50

67/54

LPT192-804

Y

192

88,740

510

3,200

4.0

46

Not listed

LPT330-806

Delta

330

115,070

890

10,800

22.8

59

2 × 67/54

LPT300-806

Y

300

87,100

660

10,800

13.2

53

Not listed

LPT290-806

Delta

290

70,750

510

1,960

11.7

52

2 × 67/54

LPT240-806

Y

240

86,000

510

4,800

11.7

48

Not listed

LPT396-806

Delta

396

109,620

890

6,900

22.8

59

2 × 67/54

LPT360-806

Y

360

79,020

660

6,900

13.2

53

Not listed

LPT348-806

Delta

348

67,330

510

4,800

6.0

52

2 × 67/54

LPT288-806

Y

288

29,540

510

2,940

6.0

48

Not listed

Configurations

Configured Around
What You Store

Choose the temperature version first, then add the upgrades your site and product need. Every option is built and tested in the factory, not retrofitted on site.

  • 0 → +15 °C

    Chilled Storage

    Fruit, vegetables, flowers, dairy and beverages — humidity-friendly air distribution.

    01
  • −18 → −25 °C

    Frozen Storage

    Meat, seafood, ice cream and frozen food, with heated door frames and pressure relief.

    02
  • Down to −40 °C

    Blast Freezer

    High-capacity unit and airflow for fast pull-down of fresh product to core temperature.

    03
  • Chill + Freeze

    Dual-Zone Room

    An insulated partition splits a 40HQ into two rooms, each with its own refrigeration.

    04
For an Accurate Quotation, Please Provide:

Based on this information, the cold storage box and refrigeration configuration can be matched to the buyer’s vehicle and operating conditions.

  • Required internal or external box dimensions
  • Required storage temperature
  • Type of products to be transported
  • Vehicle type and cargo area dimensions
  • Required quantity
  • Available power supply
  • Daily operating time
  • Local ambient temperature
  • Required battery or solar configuration
Applications

Where It Works Best

The Portable Cold Storage Box for Tricycles, Vans & Pickup Trucks is suitable for transporting and storing temperature-sensitive products such as:

How We Deliver

From Inquiry to Cold Storage

  1. 01

    Requirement Review

    Product, target temperature, daily loading and site power supply.

  2. 02

    Design & Quotation

    Heat-load calculation, layout drawing and a configured quotation.

  3. 03

    Production & Testing

    Built in our factory and pull-down tested before it is released.

  4. 04

    Shipping & Documents

    Ships as a standard container with export and customs paperwork.

  5. 05

    Start-Up Support

    Remote commissioning guidance and long-term spare parts supply.

FAQ

Frequently Asked Questions

  • What is a PT-type condenser?

    The source page describes a PT-type condenser with a flange-connected tube-bundle assembly that can be withdrawn for inspection, cleaning or repair. Confirm the exact construction and official product designation with the manufacturer.

  • What capacity range is listed?

    The source table lists nominal heat-rejection values from 48 kW to 396 kW. These values should be verified against the rated operating conditions before equipment selection.

  • What does the removable tube bundle help with?

    It can provide access to heat-transfer surfaces for inspection and cleaning, potentially simplifying maintenance. The actual process depends on the equipment design, piping arrangement and safe isolation procedure.

  • What electrical information should be confirmed?

    Confirm supply voltage, frequency, phase, motor wiring, rated current, total fan power and protection requirements using the approved wiring diagram and nameplate.

  • What information is required to select a model?

    Provide the required heat rejection, refrigerant or heat-transfer medium, inlet and outlet conditions, ambient conditions, electrical supply, piping details and available maintenance clearance.

Start Your Project

Tell Us What You Store.
We'll Engineer the Cold.

Send your storage temperature, room size and location — our engineers reply with a configured solution and quotation within 24 hours.

  • Free Equipment Selection
  • Custom System Design
  • Response Within 24 h